2-4 Sun StorEdge A1000 and A3x00/A3500FC Best Practices Guide November 2002
The total SCSI bus length for this example is 24.4 M. It is calculated as follows: each
SCSI cable’s length (Cable no. 1 + Cable no. 2 + Cable no. 3) + the internal SCSI bus
length of each device (Host no. 1 + A3x00 no. 1 + A3x00 no. 2 + Host no. 2).
FIGURE 2-1 SCSI Bus Length Calculation
Each A3500FC is shipped from the factory with one pair of 15 meter fiber-optic
cables. The product will support a multi-mode fiber-optic connection up to 500
meters long using short wave GBICs only. The use of long wave GBICs is supported
but the connection must be through a switch to the host processor (
FIGURE 2-2). Refer
to the switch documentation for the maximum cable length for the long wave GBIC
connection.
FIGURE 2-2 Fibre Channel Connection With Long Wave GBIC Support
2.1.6 SCSI ID, Loop ID, Controller, and Disk Tray
Switch Settings
The factory default setting for controller A is SCSI ID 5 (T5) and for controller B is
SCSI ID 4 (T4). The SCSI cables connected within a SCSI daisy chain configuration
should be crossed to avoid SCSI ID conflicts (see Section 1.2.2 in the Sun StorEdge
A3500/A3500FC Hardware Configuration Guide).
Host no. 2
Cable no. 1 (8.0 M)
(0.1 M)
(0.1 M) (0.1 M)
(0.1 M)
Cable no. 3 (8.0 M)
A3x00 no. 1
A3x00 no. 2
Host no. 1
Cable no. 2 (8.0 M)
Switch
Host
A3500FC
Short wave GBIC connection (500 M max)
Long wave GBIC connection
Processor